Safety and ATEXAnalysis
Seveso III and biogas plants: flammable gas thresholds and calculating the biogas inventory on site
When can a biogas or biomethane plant approach the thresholds of the Seveso III Directive? An illustrative look at how to calculate the mass of biogas on site.
Other language versions: Polski, Deutsch, Español, Français, Italiano, Nederlands.

A biogas plant is usually not a Seveso establishment, but this conclusion may be adopted only after doing the calculation. Directive 2012/18/EU (Seveso III) sets obligations for establishments in which the quantity of dangerous substances reaches or exceeds the thresholds in Annex I. As the scale of installations grows – biomethane plants, compression, liquefaction – the subject returns. The calculation below is illustrative: the classification is determined for a specific establishment, on the basis of its data and the current regulations.
How the Directive's thresholds work
The Directive distinguishes lower-tier establishments (increased risk, the lower threshold) and upper-tier establishments (high risk, the higher threshold). Dangerous substances are divided into categories, and for each two threshold quantities are given. For the physical hazard category P2 (flammable gases of category 1 or 2) the thresholds are 10 tonnes for lower-tier establishments and 50 tonnes for upper-tier establishments. In Polish law the Directive was implemented through the Environmental Protection Law (Prawo ochrony środowiska) and implementing regulations; the current definitions and obligations should be checked there.
Biogas is a mixture of gases, of which the flammable one is methane (usually about 50–65 % by volume), plus small amounts of other components. How the mixture is classified requires establishing its properties, and for gas containing hydrogen sulphide, toxicity must also be considered. For this reason, in practice the classification is carried out by a person familiar with the rules on the classification and labelling of substances and mixtures.
How to calculate the mass of biogas
The mass of gas is the product of volume and density. The density of biogas depends on its composition: methane has about 0.72 kg/m³ under normal conditions, carbon dioxide about 1.98 kg/m³, so a mixture of 55 % CH₄ and 45 % CO₂ has a density of the order of 1.3 kg/m³, and at 65 % methane it falls to about 1.15–1.2 kg/m³. For an illustrative calculation a range of 1.1–1.3 kg/m³ is assumed, and at an overpressure of the order of several tens of millibars the correction is negligible compared with the uncertainty.
The volume includes:
- Gas storage (membrane roof, freestanding tank) – on the conservative principle, the maximum capacity is taken, not the typical fill level.
- The gas space of the digesters and digestate tanks, if connected to the gas system.
- Pipelines – volume from length and diameter; usually small compared with the storage.
- Additional tanks and pressure buffers.
An example of the method: a storage of 3000 m³ and digester gas spaces totalling about 2000 m³ gives 5000 m³; at 1.2 kg/m³ that is about 6 t of biogas, of which methane is 3–4 t. The result lies below the 10 t threshold, but is of the same order of magnitude, so expanding the storage may change the assessment. This is only an illustration of the method, not data of any specific installation.
What a biomethane plant and bioLNG change
A biogas upgrading installation increases the amount of flammable gas in the establishment in two ways: it creates additional buffers of biomethane with a higher methane content (about 95–99 %) and higher energy density, and it introduces compression, in which the mass contained in the tanks grows in proportion to the pressure. A few dozen cubic metres of tank at a pressure of the order of 200–250 bar is several hundred kilograms to a few tonnes of methane. Liquefaction (bioLNG) means that liquefied gas tanks with a capacity of tens of cubic metres hold outright over ten tonnes of gas: 1 m³ of LNG weighs about 0.42–0.45 t, so a 50 m³ tank is roughly 21–22 t. Here the 10 t threshold is exceeded by a small tank.
The conclusion: a typical agricultural biogas plant with cogeneration usually remains below the thresholds, whereas a biomethane plant with a large buffer, a compression station or a liquefaction installation requires analysis already at the concept stage.
The summation rule
The assessment does not count a single substance alone. The summation rule in the Directive concerns substances of the same hazard category and takes into account all substances present in the establishment, including on neighbouring installations belonging to the same operator. The sum includes, among others, biogas, biomethane, propane for enrichment, heating oil (category depending on properties), ammonia, if present, and other substances. The sum indicator is calculated for the hazard groups: health, physical and environmental. The boundaries of an establishment are a legal concept that may cover several installations under one management.
What exceeding a threshold means
An establishment classified as lower-tier has, among other things, the obligation to notify the authorities, to draw up a major accident prevention policy and to run a safety management system. An upper-tier establishment additionally prepares a safety report and an internal emergency plan and is subject to more frequent inspections, while the authorities prepare external plans and inform residents. The detailed scope, deadlines and competent authorities follow from Polish regulations; they should be checked in their current wording. Exceeding a threshold is not a penalty – it is a signal that the scale of the hazard requires a systematic approach.
A practical procedure
- Take an inventory of dangerous substances and their maximum quantities.
- Establish the classification of biogas, biomethane and the other substances.
- Calculate the sums by category.
- Compare with the thresholds and record the assumptions (this is the document that will be needed during an inspection).
- Analyse expansion plans: an additional tank may change the classification.
- If close to the thresholds, consult the authority or an adviser on the classification.
Typical mistakes
- Counting only the average fill level instead of the maximum quantity.
- Omitting propane, heating oil or other substances from the sum.
- Assuming that "biogas is not on the list", without checking the category of the mixture.
- No update of the calculations after expansion.