CHP unit vibration and noise: foundation, silencers, enclosure and noise limits
A CHP unit generates vibration and noise from the exhaust, air supply, coolers and enclosure. We discuss the sources, foundation, silencers and measurements at the site boundary.
Other language versions: Polski, Deutsch, Español, Français, Italiano, Nederlands.

The noise of a CHP unit comes mainly from the exhaust, the supply and exhaust air and the external coolers, and the vibration from the operation of the engine and is transmitted through the foundation and the pipework. A typical gas engine without an enclosure emits a sound level in the order of 90–105 dB(A) at a distance of 1 m, and after an enclosure and silencers are fitted several dozen decibels less. The values depend on output and manufacturer; we give them as an indication.
Noise sources
- Exhaust outlet. The loudest element, especially at low frequencies. It requires a reactive and absorptive silencer, often in two stages.
- Supply and exhaust air of the engine room. Air ducts and fans carry noise from the inside to the outside; duct silencers or splitter attenuators are used.
- External coolers. The cooler fans are a source of broadband noise that rises with rotational speed; it is reduced by speed control and a lighter night-time load.
- Enclosure and walls of the engine room. The noise radiated by the unit passes through walls, doors and gates; lightweight walls without insulation are poor.
- Pipework and fittings. Pulsations of gas and water cause pipe vibration and secondary noise.
Foundation and vibration isolation
The unit is usually mounted on a massive reinforced concrete foundation with a mass at least several times greater than the mass of the unit, laid on ground with good bearing capacity and separated from the hall floor by an expansion joint. The use of resilient mounting (pads, springs, vibration isolators) reduces the transmission of vibration to the building, and the unit manufacturer states the requirements. The exhaust, water and gas pipework is fitted with expansion joints, and wall penetrations are sealed flexibly. Cable connections should have slack.
Enclosure and engine room
Two approaches: a containerised unit with a factory sound-absorbing enclosure, or a building with acoustic insulation. In both cases tightness is what counts: ventilation openings are fitted with silencers, doors are sealed and penetrations are sealed with compound. A typical enclosure reduces the sound level by 20–30 dB in the high band, less in the low band. Remember the ventilation and ATEX requirements, which must not be sacrificed for acoustics.
Noise requirements
The permissible environmental levels are set by a regulation issued under the Environmental Protection Law (Prawo ochrony środowiska, the Polish act on environmental protection); they depend on the designated use of the area (single-family housing, farmstead, service development) and on the time of day and night, and for industrial plants equivalent levels for day and night apply. Night-time limits are usually stricter by several to a dozen or so decibels. In case of doubt, the current wording of the regulations and the provisions of the environmental decision and permit should be checked. The legal situation on the date of the entry may change.
The engine exhaust system, including the silencer and the stack, is discussed in the article Biogas engine exhaust system, and the removal of air from the engine room in Ventilation of a CHP engine room.
Measurements and corrective actions
- Baseline measurement: a measurement of background noise before construction and a measurement after commissioning at the site boundary or at the points indicated in the decision, at full load and at night.
- Spectrum analysis: octave bands show whether a low tone from the exhaust or the noise of the fans dominates.
- Measures: improving the sealing of the enclosure, an exhaust silencer with greater attenuation, limiting the cooler speed at night, moving the outlet away from residential development, an acoustic screen.
- Vibration: measuring acceleration on the foundation and on the pipework; trends since the last inspection indicate loosening of fixings or wear of the vibration isolators.
Typical mistakes
- Omitting a silencer in the engine room ventilation system.
- A rigid connection of pipes to the unit.
- Measuring only in the daytime, when the night-time limit is stricter.
- Relocating a cooler without recalculating the noise.
Order of actions on a complaint
When neighbours report noise, do not start by buying a silencer. First measure the levels at the point of complaint and at the site boundary, including at night, and identify whether the exhaust, the ventilation or a low tone transmitted by vibration dominates. Then check the condition of the elements that may have changed: worn vibration isolators, damaged door seals, a changed cooler speed. Only then choose a measure. Record the results, because they will make the conversation with the authority and with residents easier.
Design guidance
In the design it is worth demanding from the supplier the noise spectrum of the exhaust, the supply air and the enclosure in octave bands, and not only the total dB(A) value. This makes it possible to match the silencers to the dominant bands. The location of the exhaust outlet and the coolers is planned on the side furthest from residential development, and the direction of the outlet is turned away from buildings. Acceptance measurements should be planned in advance, together with the operating conditions in which they are to be carried out.
Summary
Well-designed acoustics are cheaper at the design stage than a repair after neighbours' complaints. Plan the enclosure, silencers and foundation together with the ventilation, and confirm compliance with measurements in the worst-case conditions.