Synchronous generator protection at a biogas plant: faults, loss of mains and abnormal operation
The generator at a biogas plant is protected by a set of relays against faults, loss of mains and abnormal operation. We discuss protection functions, DSO settings and periodic tests.
Other language versions: Polski, Deutsch, Español, Français, Italiano, Nederlands.

A synchronous generator at a biogas plant is protected by a set of relays that disconnects it from the grid or stops the engine on short circuits, loss of mains and operation outside permissible parameters. For the operator it is important to understand which protection has operated, why, and whether its setting is correct. Below we describe the range of functions in conceptual terms; the specific function numbers and settings are determined by the designer and the distribution system operator.
Protection against short circuits and overloads
- Time-delayed overcurrent protects against overload; it responds after a time that depends on the current.
- Short-circuit overcurrent responds to short circuits inside the system and in the grid; the settings are coordinated with the protection of the grid and the transformer (selectivity).
- Differential compares the currents flowing into and out of the winding; for larger generators it quickly detects a phase-to-phase fault in the winding.
- Earth faults depend on the way the neutral point is earthed; they require separate current transformers and settings, and the sensitivity depends on the earthing impedance.
Protection against abnormal operation
- Reverse power. If the engine loses fuel or ignition, the generator may begin to run as an electric motor, driving the combustion engine from the grid. This is dangerous for the engine (risk of damage, accumulation of mixture) and for the gas installation; the protection disconnects the generator after a short time.
- Loss of excitation. The generator draws reactive power from the grid and overheats the rotor and the winding ends; the protection disconnects it or limits it.
- Current unbalance (negative sequence component). It aggravates rotor heating; time-delayed protection.
- Overexcitation (V/Hz). It protects the core against saturation at low frequency and high voltage.
Voltage and frequency protection
Over- and undervoltage and over- and underfrequency functions result mainly from connection requirements. The settings and operating times are specified by the DSO in the connection conditions; they are meant to allow operation within the ranges of normal deviations and to disconnect the generator when the grid goes outside the permissible limits. The general rules for generating units are set by the RfG regulation, but national requirements implement the details.
Protection against island operation
When the grid is disconnected by the switching off of a line, the generator could continue to supply local loads or, worse, a disconnected part of the network. The protection detects this state by means of:
- ROCOF (rate of change of frequency), the value of which rises during island operation when the power balance is disturbed,
- voltage vector shift, that is a sudden change of the phase angle,
- remote signals or interlocks from the circuit breakers on the DSO side.
Settings that are too sensitive cause false trips on disturbances in the grid, settings that are too lenient increase the risk of island operation. For this reason the settings are agreed with the DSO.
Settings and tests
- Documentation: the relay settings sheet, the diagram, the range, the software version.
- Periodic tests: checking the operation of each function by injecting current and voltage with a relay tester; the interval follows from the manufacturer recommendations and the DSO requirements, often once every few years and after every change of settings.
- Event recording: the relay records events and waveforms; after a trip they should be secured before restarting.
- Change management: every change of settings approved and documented.
Typical pitfalls
- Reclosing after a trip without establishing the cause.
- An overcurrent setting not adjusted after a change of transformer rating.
- No test of the reverse power function, which requires a safe forcing of the conditions.
- A change of the current transformer ratio without correcting the settings.
- A relay software update without verifying the settings.
How to read a trip event
After a protection operates, the relay records the type of function, the values of currents and voltages and the time. First check whether it was a grid event (a voltage dip, a frequency change) or a local one (a short circuit, a loss of fuel). Repeated trips of the same function in similar conditions point to a setting or a change in the grid, and a single one to a disturbance. The events are worth comparing with the DSO messages and with the records of the engine controller. Reclosing is attempted only after the cause has been established.
Cooperation with the grid operator
The connection conditions usually contain the required functions and setting ranges, and a change of output or of the configuration of the installation may require them to be updated and accepted by the DSO. Before restarting after a modernisation, hand over the relay test reports and the diagram. Keep the versions of the settings sheets and the confirmations from the DSO, because in a dispute over the cause of a shutdown they show which settings were in force.
Summary
Generator protection is not an add-on but a condition for being permitted to run in parallel with the grid. The operator should know the list of active functions, have current settings sheets and plan the tests. All work on protection systems should be carried out by persons with electrical qualifications. The connection procedure and the arrangements with the DSO are described in the article Connecting a biogas plant to the power grid.