Heat buffer tank at a CHP unit: capacity, stratification and control
A heat buffer lets the CHP unit run flexibly while the consumer receives heat without interruption. We show how to size the capacity, stratification and safeguards.
Other language versions: Polski, Deutsch, Español, Français, Italiano, Nederlands.

A heat buffer tank is a water store that holds the heat from the CHP unit and releases it to the consumer when it is needed. Without a buffer, the CHP unit has to follow the heat demand or dump the excess to an emergency cooler. With a buffer, it can run according to the electricity needs, and the heat is used with a delay. Below we discuss capacity sizing, stratification and control.
Why a buffer at the CHP unit
Three typical situations: flexible operation (the CHP unit is stopped during low-price hours and heat must still be delivered), start-up and shutdown of the CHP unit (heat with a smoothly rising temperature), and a consumer with variable demand, for example a batch dryer. A buffer also smooths the short switching cycles of the backup boiler and reduces the number of pump starts.
Sizing the capacity
Thermal energy stored in water: Q = V · ρ · c · ΔT. For water ρ ≈ 1000 kg/m³ and c ≈ 4.19 kJ/(kg·K), so 1 m³ of water at ΔT = 25 K stores about 29 kWh.
Illustrative example. A CHP unit with a thermal output of 500 kW is to be switched off for 4 hours, and the consumer draws an average of 300 kW during that time. Required energy: 4 h × 300 kW = 1200 kWh. At ΔT = 25 K: V = 1200 / 29 ≈ 41 m³. At ΔT = 20 K about 52 m³ is needed. To this is added a margin of 10–20% for incomplete use of the volume (the mixing layer) and for losses.
The heat balance of the whole installation, including the seasonality of heat use, is discussed in the article Waste heat from a biogas plant CHP: balance and seasonality.
Conclusion: the capacity in the balance grows linearly with the length of the interruption and inversely with the temperature difference. A high flow temperature and a low return temperature mean a cheaper tank.
Stratification
In the tank, hot water (lighter) settles at the top and cold water at the bottom. The sharper the boundary (the thermocline), the more energy can be drawn at full temperature.
- Inlets and outlets should have a low flow velocity (typically below about 0.1–0.2 m/s at the inlet), which limits mixing.
- Deflectors or diffusers at the inlets disperse the stream.
- A slender tank (a higher height-to-diameter ratio) favours stratification, but it is limited by structural considerations.
- The pump flow is chosen so as not to force excessive velocities; avoid feeding return water with a large temperature difference into the middle of the tank.
Insulation and standing losses
The tank should have thermal insulation, usually 100–200 mm thick (mineral wool or foam), with a protective jacket and a tight seal at the nozzles, because thermal bridges dominate the losses. Standing losses are in the order of several to a dozen or so watts per square metre of surface at a temperature difference of several dozen kelvins, so for a tank with a capacity of 40 m³ usually about 0.5–2 kW. They are worth calculating, because they act around the clock.
Sensors and charging strategies
The minimum is three temperature sensors at different heights (top, middle, bottom); four or five are better, so that the controller can estimate the state of charge. A typical strategy: the CHP unit starts when the bottom sensor exceeds the limit value (the buffer is discharged) and stops when the bottom sensor shows heat (the buffer is charged). In flexible mode an energy price schedule is overlaid on this. A backup boiler or an emergency cooler protects against exceeding the temperature.
Safeguards
- Open or pressurised tank: closed systems need a safety valve, an expansion vessel and a pressure gauge; pressure equipment is subject to the requirements of the PED directive and to technical inspection regulations, depending on the parameters.
- Overheating protection: a temperature limiter independent of the main controller.
- Venting, drain and access for cleaning; anti-corrosion protection of the water (treatment).
Typical mistakes in practice
The most common problems are a tank that is too small for flexible operation, return water fed into the middle of the tank, missing insulation on nozzles and fittings, and sensors mounted too close to the inlets, which show the temperature of the stream and not of the layer. It also happens that the backup boiler feeds the buffer from the bottom and mixes the layers, destroying stratification. With a consumer with a low return temperature the value of the buffer increases, so it is worth checking the control of the consumer's valves. After commissioning, record the temperature profile over a day and compare it with the design assumptions. It is worth repeating the record in winter and in summer, because with a different heat demand the position of the thermocline and the number of CHP starts change. If the buffer works together with a backup boiler, check that the boiler does not start more often than the schedule implies.
Summary
A buffer is an inexpensive part of the installation compared with the CHP unit, yet it determines flexibility and the quality of heat delivery. Capacity is calculated from the balance and ΔT, stratification is maintained through the choice of inlets and velocities, and the safeguards are agreed with the designer and the technical inspection. The numerical values in the article are indicative.