Tanks and membranesAnalysis

Biogas plant tanks and building law: permit, acceptance and periodic inspections of the structure

A digester tank is a construction structure, so it is subject to a permit, acceptance and periodic inspections. We discuss the relationship to technical supervision and ATEX.

Published 5 min readFeedstockData Editorial Team

Other language versions: Polski, Deutsch, Español, Français, Italiano, Nederlands.

Sala posiedzeń Sejmu RP widziana z boku – amfiteatralny układ ław poselskich i kamienna okładzina ścian w ciepłym świetle.
Photo Adrian Grycuk / Wikimedia Commons, licence CC BY-SA 3.0 pl, source file; changes: cropping

Biogas plant operators often treat the digester tank as process equipment, whereas in the regulations it is also a construction structure, with the obligations that follow from this. The permit, acceptance and periodic inspections follow from the Building Law (Prawo budowlane, the Polish construction act), and alongside them separate regulations on technical supervision and explosion protection apply. The text below puts these regimes in order according to the legal position as of October 2026. It is not legal advice; the current wording of the act and the regulations must always be checked and doubts consulted with the site manager, an expert or a lawyer.

The tank as a construction structure

Under the Building Law, a construction structure (obiekt budowlany) is, among other things, a civil engineering structure (budowla), that is, a structure that is neither a building nor a small architectural object, including tanks. Consequently a biogas plant tank is subject to the general requirements for design, execution, maintenance and acceptance. These include the basic requirements: structural safety, fire safety, safety in use, environmental protection and adequate durability.

Permit and acceptance

Construction of a tank in principle requires a building permit, issued on the basis of a building design prepared by qualified designers. The biogas plant as a whole often requires environmental decisions and other approvals, but this topic goes beyond the scope of the article. After construction is completed the investor:

  1. notifies the competent authority of the completion of construction or applies for an occupancy permit, depending on the category of the structure and the regulations;
  2. submits the as-built documentation, the site manager's statement and the records of tests and checks;
  3. obtains the ability to begin use when the authority raises no objection or issues the permit.

For tanks the important documents are the tightness test records, concrete tests, the material documentation of the membrane and the acceptance records of the electrical and gas installations. The category of the construction structure affects the procedure; it must be read from the annex to the act and from the design documentation.

Periodic inspections under Article 62

Article 62(1) of the Building Law obliges the owner or manager of a structure to maintain it in proper technical condition and to carry out periodic inspections. In general the following are distinguished:

Type of inspection Frequency Subject
Annual inspection at least once a year technical condition of elements exposed to harmful weather effects and to the destructive action of factors occurring during use of the structure; installations and equipment serving environmental protection
Five-year inspection at least once every 5 years technical condition and fitness for use of the structure, aesthetics and surroundings, as well as testing of the electrical and lightning protection installation

The scope of the inspection, the persons authorised to carry it out (persons with building qualifications in the relevant specialisation) and the details are set out in the act. In practice the annual inspection of a tank covers a visual check of the walls, top of the wall, slab, expansion joints, seals, membrane fixing and steel elements, and the five-year one — a broader assessment of the structure and, where applicable, supplementary tests.

The building log book

The owner or manager of a structure is obliged to keep a building log book (książka obiektu budowlanego), in which data on the structure, inspections, repairs, failures and other important information are recorded. A well-kept log book is a document of first choice during an inspection by the building supervision authority and when settling a loss. For tanks it is worth placing in it photographs and records of settlement checks, membrane inspections and seal replacements.

The procedure for the permit and use of the entire biogas plant is described in a separate article on building permit for a biogas plant step by step; here we focus solely on the tank and its periodic inspections.

Technical supervision and the building inspection

The building inspection concerns the structure as a construction. Technical supervision (dozór techniczny), on the other hand, concerns technical devices specified in the act on technical supervision, e.g. some pressure vessels or gas equipment. A low-pressure biogas tank (of the order of millibars) is usually not pressure equipment within the meaning of these regulations, but accompanying installations, such as cylinders or compressed gas tanks, may be. The scope of obligations for a specific installation must be determined on the basis of its parameters, and we describe supervision issues in the article on technical inspections and UDT supervision.

ATEX and occupational safety

The third regime results from the regulations on explosion protection. Directive 1999/92/EC imposes on the employer an obligation to assess the explosion risk, classify zones and prepare an explosion protection document. For a tank this means designating zones around the roof, valves and penetrations and selecting equipment suitable for the zones. These obligations do not replace building inspections, and building inspections do not replace the ATEX document. The details are discussed in the article on ATEX at a biogas plant.

Practical conclusions

  • It is worth keeping a common inspection calendar covering building, supervision, electrical and ATEX inspections and membrane checks.
  • Annual and five-year inspections should be commissioned from persons with the appropriate qualifications, and the records archived.
  • Before buying a biogas plant or tank, check whether permits, acceptance records and the building log book are available.
  • In case of doubt about the category of the structure or the scope of inspections, consult the designer or an expert rather than general descriptions.

The provisions of the Building Law are amended from time to time, so the rules cited in the article are treated as an indicative framework which must always be compared with the current text of the act.

Sources

  1. Internetowy System Aktów Prawnych - Prawo budowlane (ustawa z 7 lipca 1994 r.)
  2. Dyrektywa 1999/92/WE (ATEX 137)
  3. Główny Urząd Nadzoru Budowlanego