Tanks and membranesExplainer

Foundation and ground under a digester tank: settlement, groundwater buoyancy and drainage

A full tank loads the ground heavily, and an empty one can be pushed up by water. We explain geotechnical investigations, settlement, buoyancy and inspection drainage.

Published 4 min readFeedstockData Editorial Team

Other language versions: Polski, Deutsch, Español, Français, Italiano, Nederlands.

Słoiki z próbkami substratów – kiszonką, trawą, gnojowicą i odpadami spożywczymi – na stalowej tacy w laboratorium.
Illustration: FeedstockData (AI, Google Gemini)

A digester tank with a diameter of several dozen metres and a height of a few metres, filled with a liquid of a density close to that of water, exerts on the ground a pressure of the order of several dozen kilopascals. The durability of the tank is determined not only by the walls and the membrane, but also by the ground under the slab: its bearing capacity, deformability and water level. Errors in this layer reveal themselves after years, as cracks, tilting or damaged pipes, and repair is difficult and expensive.

Geotechnical investigations as the starting point

Foundation design in the European Union is based on the Eurocode 7 standards (EN 1997) together with national annexes. The framework of the procedure includes ground investigation: boreholes, soundings, laboratory tests of samples and an assessment of the groundwater level, including its seasonal fluctuations. The result is geotechnical documentation, which defines the soil layers, their parameters and recommendations for foundation seating.

The scope of the investigations depends on the geotechnical category of the structure and the ground conditions; for large tanks with liquid, higher categories are usually applied than for simple farm buildings. Detailed requirements follow from national regulations and the designer's decisions.

Foundation slab and bearing capacity

A typical tank stands on a reinforced concrete slab, which spreads the load from the walls and the liquid onto the ground. The slab can be supported on native ground, on a reinforced sub-base or on piles. The designer checks:

  1. the bearing capacity of the ground with a full tank and additional loads (snow, wind, gas pressure);
  2. total and differential settlement;
  3. stability, including possible sliding or tilting;
  4. the effect of groundwater on the parameters of the ground and the slab.

Weak soils are particularly dangerous: peats, organic soils, uncontrolled fills, swelling or collapsible soils. In such conditions soil replacement, ground improvement or pile foundations are used.

Uneven settlement and its effects on the installation

Uniform settlement is usually acceptable if it does not cause clashes with the connections. Uneven settlement is dangerous: the tank tilts, the wall works in bending, and the pipes connected to the tank are loaded by displacement. In practice this means:

  • cracks in the walls and slab and leaks at expansion joints;
  • stresses on pipes, penetrations and flanges, which increases the risk of leaks;
  • uneven loading of the membrane and its fixing, if the top of the wall is no longer level;
  • changes in the inclination of agitators and problems with their operation.

For this reason pipes and connections are designed with the ability to compensate for movements (flexible couplings, expansion joints), and during operation levelling of benchmarks on the top of the wall is used to detect changes. A measurement once a year for the first few years is a cheap way of detecting a problem earlier.

Groundwater buoyancy

An empty tank, especially one sunk into the ground or founded in ground with a high water level, can be pushed up by groundwater. The buoyant force is equal to the weight of the displaced water, so an empty tank has only a small weight reserve relative to the buoyant force. In the design the stability condition against uplift in the emptied state is checked, and if necessary anchoring, loading of the slab or drainage lowering the water level is used.

For the operator the conclusion is simple: before emptying a tank for an overhaul, it must be checked what the groundwater level is and whether the tank may be emptied completely. After the spring thaw or heavy rainfall the risk is higher. In case of doubt the emptying procedure is determined by the structural designer.

Inspection drainage and insulation

Under the tank slab a drainage layer with pipes and inspection manholes is often made. It serves for:

  • observing possible leaks from the tank bottom (the presence of digestate in a manhole is a signal of failure);
  • lowering the groundwater level during an overhaul;
  • draining rainwater from the sub-base.

The drainage requires inspection: the manholes should be accessible and their contents assessed periodically, e.g. by smell, colour, conductivity or pH. A result that departs from the norm requires verification. Observation of the drainage is also an element of water and ground protection.

Cracks and leaks in concrete resulting from uneven settlement are described in the article on cracks in tank concrete, and the requirements for concrete – in the text on watertight concrete. The tightness test before start-up is described in the article on the water test of a tank.

What to pay attention to when buying and operating

  • Geotechnical documentation should be part of the design documentation, and not just a formality.
  • It is worth asking the contractor about the assumptions regarding the water level and the emptying procedure.
  • Benchmarks for measuring settlement should be installed at acceptance and described.
  • With unusual ground it is better to pay for a more thorough investigation than to repair the tank after years.

Knowledge of the ground is not attractive, but in the case of tanks with liquid it largely decides whether the structure survives its planned service life.

Sources

  1. FNR - Fachagentur Nachwachsende Rohstoffe (Leitfaden Biogas)
  2. JRC - Eurokody: Eurokod 7, projektowanie geotechniczne (EN 1997)
  3. KTBL - Biogas (Kuratorium für Technik und Bauwesen in der Landwirtschaft)