Detection of flammable gases and CO₂ at a biogas plant: sensor types, alarm thresholds and placement

We compare catalytic, infrared and semiconductor sensors at a biogas plant and discuss alarm thresholds, sensor placement and calibration.

Published Updated 4 min readFeedstockData Editorial Team

Other language versions: Polski, Deutsch, Español, Français, Italiano, Nederlands.

Izolowane rury spalin i wymienniki na dachu zielonego kontenera CHP, w tle komin.
Photo Photograph by Clem Rutter, Rochester, Kent. ( www.clemrutter.net ). / Wikimedia Commons, licence CC BY-SA 3.0, source file; changes: cropping

Stationary gas sensors are meant to detect a leak before the concentration reaches a dangerous level and to trigger a response: an alarm, ventilation, shutdown of equipment or isolation of the gas supply. The effectiveness of detection depends less on the number of sensors than on matching the technology to the conditions, placement consistent with the physics of the gas and calibration discipline. This guide covers flammable gases and CO₂; detection of H₂S for people is a separate topic.

Three technologies and their limitations

Technology Principle Advantages Limitations
Catalytic (pellistor) combustion of gas on a heated element, change in resistance low price, widely used, good linearity up to LEL requires oxygen, prone to poisoning (siloxanes, sulphur compounds, silicones), requires frequent calibration
Infrared (NDIR) absorption of radiation by CH₄ or CO₂ molecules works without oxygen, resistant to poisoning, long service life higher price, sensitive to vapour condensing on the optics, measures only IR-absorbing gases
Semiconductor change in conductivity of a metal oxide sensitive at low concentrations low selectivity, influenced by humidity and temperature, rarely used for explosion safety tasks

For rooms with biogas where siloxanes and hydrogen sulphide are present, NDIR sensors are usually a safer choice than catalytic ones. In systems where methane is expected only in traces, for example in an engine hall, a pellistor is sometimes sufficient, provided its condition is monitored. Electrochemical cells are used to measure oxygen, and NDIR sensors for CO₂.

Alarm thresholds

Flammable gas concentrations are given as a percentage of the lower explosive limit (% LEL). A typical arrangement looks like this:

  • about 10 % LEL: pre-alarm; signalling and increased ventilation,
  • about 20 % LEL: main alarm; shutdown of equipment that could be ignition sources, closing of shut-off valves, evacuation from the room.

This is practice, not a direct requirement; the final settings are set by the explosion protection document, taking into account the response time of the system and the nature of the room. For CO₂ and oxygen, thresholds are selected to protect people: an alarm when the oxygen concentration falls to around 19.5 %, and for CO₂ according to the limit values in the current regulation on maximum permissible concentrations.

Placement based on the physics of the gas

Methane is lighter than air, so flammable gas sensors are mounted high: under the ceiling, above potential leak points, in the upper part of the hall and above the roof. Biogas is a mixture with a density close to that of air, so in enclosed rooms two sensor levels are often used. CO₂ is heavier, so its detectors are placed low, in sumps, ducts and depressions.

Important rules:

  1. The sensor is placed where gas will actually collect, not where it is convenient to reach. Airflow from a fan can blow gas away from the sensor.
  2. Near chimney and roof air inlets, avoid obstructing the sensors.
  3. Sensors need service access; if reaching them means climbing a ladder without protection, calibrations will be postponed.
  4. For rooms with a large floor area, the number of sensors is chosen on the basis of simulation or dispersion analysis.

Response times and integration with ventilation and gas shut-off

Sensors have a response time t90 of the order of a dozen or so seconds to over a minute, which must be accounted for in the whole chain. The alarm should activate emergency ventilation and gas shut-off valves, if the explosion protection document so provides. The action logic should be fault tolerant: a cable break or loss of power should result in a safe state (an alarm), not silence.

Calibration and functional test

Two procedures are distinguished. A functional test (bump test) consists of applying reference gas and checking whether the sensor responds and triggers the alarms; it is performed more often, often quarterly or according to the instructions. Calibration sets zero and sensitivity and is performed less often, usually every several to a dozen or so months, depending on the technology and conditions. Intervals are chosen on the basis of the manufacturer's recommendations and observed drift, and every result is recorded in a logbook.

Typical mistakes

  • A pellistor sensor in an environment with siloxanes and hydrogen sulphide, never calibrated.
  • A sensor mounted low for methane or high for CO₂.
  • Covering of the sensor or dust guard, or flooding of the enclosure during washing.
  • Switching off an alarm because of false readings instead of finding the cause.
  • No link to ventilation and gas shut-off: the alarm just "flashes" in a control room that nobody watches.

Well-maintained detection does not replace zones or discipline in work, but it can turn a serious event into a minor failure if it acts in time.

Sources