Cogeneration and enginesExplainer
Electrical, thermal and total CHP efficiency: definitions, balance and formulas
CHP efficiency depends on what we take as the input and output of the balance. Definitions of η_el, η_th and η_tot, balance boundaries, typical ranges and pitfalls when comparing offers.
Other language versions: Polski, Deutsch, Español, Français, Italiano, Nederlands.

Cogeneration (CHP) efficiency is a measure of what share of the energy contained in the fuel is converted into useful electricity and heat. There are three basic quantities: electrical efficiency η_el, thermal efficiency η_th and total efficiency η_tot. Their values depend not only on the unit but also on how we define the input and output of the balance.
Definitions
Let P_el denote the electrical power at the generator terminals (or on the grid export side, depending on the boundary adopted), Q_th the thermal power delivered to the consumer, and Q_pal the chemical energy power of the fuel supplied to the engine. Then:
- η_el = P_el / Q_pal
- η_th = Q_th / Q_pal
- η_tot = (P_el + Q_th) / Q_pal = η_el + η_th
Fuel power is calculated as the product of the biogas flow and its calorific value: Q_pal = V̇ · H_i. For biogas it is useful to know that pure methane has a lower calorific value of about 10 kWh/m³ (under normal conditions), so biogas with a methane content of 50–60% has an H_i of about 5–6 kWh/m³. A change in CH₄ content therefore changes Q_pal and affects the result, which is why efficiency must be related to a known fuel composition and to the same reference basis (lower or higher calorific value).
Balance boundaries: what counts as "heat"
The most common mistake is mixing up available heat with used heat. In a gas engine, heat is recovered from several sources: the water jacket, the oil cooler, mixture cooling and the exhaust gas. The exhaust heat exchanger cools the exhaust to a specified temperature. If the manufacturer's declaration assumes a lower water return temperature than the plant's conditions allow, the heat "on paper" is greater than the real heat.
Total efficiency is therefore calculated in three variants, which must be distinguished:
- Heat available at the unit's output (declared in the data sheet).
- Heat delivered to the facility's internal network (after pipeline losses).
- Heat actually used (e.g. for heating the digester, a dryer, buildings), and not dissipated by emergency coolers.
For economic assessment, variant 3 counts. The article on waste heat from CHP describes how heat demand changes over the year.
Typical ranges
Gas engines fuelled with biogas, in the power range from several tens of kW to several MW, usually reach an electrical efficiency of roughly 35 to over 40% (small units usually in the lower part of the range or below), depending on power and design (larger units have higher efficiency). Thermal efficiency is usually in the range of 40–50%, and total efficiency is around 80–90% if the heat is fully utilised. These are orders of magnitude from the data sheets of various manufacturers and from the literature. For a specific installation, the manufacturer's data and measurements apply.
Electrical efficiency falls at part load and with deteriorating fuel quality or technical condition (wear, incorrect ignition). Thermal efficiency, in turn, depends on the operating conditions of the exchangers and on the return temperature.
Reference conditions
Declared efficiency applies to specific conditions: rated load, intake air temperature, fuel composition, heating water temperatures, measurement tolerance. Standards for reciprocating internal combustion engines (the ISO 3046 family) define the reference conditions and the way of declaring power and fuel consumption. When comparing offers, make sure that:
- both are prepared for the same fuel and the same calorific value,
- they include the same water temperatures and the same own losses,
- they state tolerances (often ±5% on fuel consumption),
- they distinguish power at the terminals from power delivered to the grid after deducting own needs (pumps, fans, coolers).
Efficiency versus high-efficiency cogeneration
In EU law (Directive 2012/27/EU, followed by Directive (EU) 2023/1791 on energy efficiency), the concept of high-efficiency cogeneration is not equivalent to high total efficiency, but is based on primary energy savings relative to separate production of heat and electricity, using reference efficiencies. The detailed thresholds and reference values are defined by legal acts and their implementation in the Member States. For support applications, the methods in force at the given time under the legal acts are always used, not the efficiency from the data sheet alone.
Worked example (illustrative)
Assume that 250 m³/h of biogas with H_i = 5.5 kWh/m³ flows into the engine. Fuel power is 1375 kW. The unit delivers 550 kW of electricity and 600 kW of useful heat. Then η_el = 550/1375 = 40%, η_th = 600/1375 ≈ 43.6%, η_tot ≈ 83.6%. If only half of the heat is actually used, the utilisation efficiency falls to 40% + 21.8% ≈ 61.8%.
This shows that profitability is decided not only by the unit's catalogue efficiency but also by whether and how the heat is taken off. More about the engine itself can be found in the article CHP engine: electrical, thermal and total efficiency.
Where losses come from
The remaining part of the fuel energy (usually over ten per cent) is losses: heat carried away with exhaust gas below the temperature to which it can be cooled, radiation and convection from the casing, generator losses and mechanical losses. Energy removed through emergency coolers is simply dissipated and counts as a loss in the useful balance. Losses in district heating pipes, especially long and poorly insulated ones, add to this on the consumer side. In investment assessment it is therefore worth calculating not only the unit's η_tot but also the degree of heat utilisation over the year, which depends on the seasonality of demand.
Efficiency and fuel variability
At a biogas plant the fuel composition is not constant: methane content changes with substrates, temperature and the state of the biology. The engine responds with a change in power or fuel consumption, and the automation keeps parameters within operating limits. A sensible way of reporting is to calculate efficiency from averaged data over a longer period (day, month), based on the electricity meter, the heat meter and the biogas balance taking its composition into account. A single instantaneous reading is easily distorted by flow fluctuations.
Summary
When you read a data sheet, ask: what fuel, what calorific value, what temperatures, what load, what tolerance, and what about the heat actually used. Without these answers, the η figures are not comparable.