Tanks and membranesGuide
Tank and roof monitoring: level and pressure sensors and leak symptoms in SCADA data
Sensor data tell us about the condition of the tank and roof earlier than visual checks. We explain which signals to read and which patterns mean a leak or foaming.
Other language versions: Polski, Deutsch, Español, Français, Italiano, Nederlands.

A SCADA system at a biogas plant collects hundreds of signals, but in daily work the operator looks at a few. For the tank and roof, a few signals, read together and over time, say more than individual alarms. Below we describe which of them are the most valuable, which patterns may mean a leak or foaming and how to set alarm thresholds. We discuss the general principles of monitoring and automation in the article on SCADA, sensors and alarms; here we focus on the tank.
Signals worth reading
| Signal | What it measures | What it may indicate |
|---|---|---|
| Membrane level (roof height) | volume of gas in storage | balance of production and offtake, leak |
| Gas pressure | pressure under the inner membrane | blockages, foam, valves, offtake shortfalls |
| Pressure in the inter-membrane space | condition of the outer membrane | leak, blower failure |
| Blower running time | air consumption to maintain pressure | leak, change in weather conditions |
| Temperature of contents | process stability | heating failure, winter heat losses |
| Liquid level | filling of the tank | overflow, foaming, seepage |
| Methane concentration in the inter-membrane space or at the perimeter | tightness of the inner membrane | permeability, damage |
The blower as an indicator
The blower maintains the pressure between the membranes. If the outer membrane leaks, air escapes, and the blower runs longer or more often. A good indicator is blower running hours per day, normalised to weather conditions (wind, temperature). A daily record over several weeks makes it possible to establish the normal level; a deviation by a set percentage above the norm (e.g. above 20-30 percent) can be a warning threshold. The percentage value should be adjusted to your own data, because it depends on the installation. The pressure drop after the blower is stopped, measured over a set time, is a simple tightness test of the outer membrane.
Membrane level and gas balance
The roof level shows how the gas volume changes. Regular daily fluctuations are normal, because they result from the offtake profile and temperature. The worrying patterns are:
- a gradual drop in level with constant production and offtake parameters, which may mean a leak or a drop in production;
- sudden oscillations around the maximum value, indicating valves, blockages or problems with the flare;
- no response of the roof to changes in offtake, which suggests a sensor problem or deformation of the membrane.
The balance summary: production calculated from the substrates, measured offtake and the change in volume in storage. A discrepancy greater than the measurement error requires explanation; it may mean a leak, but also an error of the flow meter.
The foaming pattern
Foaming usually produces a characteristic set of symptoms: an increase in the apparent liquid level, a rise in gas pressure, an unstable reading of the level sensors (especially ultrasonic ones), sometimes a drop in gas quality and fluctuations in CHP load. On the chart, rapid changes with an amplitude greater than usual are visible. If the pattern appears a few hours after a change in the dose or composition of the substrate, the cause is probable. Responses are described in the article on foaming in the digester, and overflow protection — in the article on overflows and level measurement.
Temperature and liquid level
The temperature of the contents is an indicator of heating operation and heat loss. A sudden drop at constant heating output may indicate too large an inflow of cold substrate or a heat exchanger failure. Changes in liquid level without changes in dosing indicate seepage or uncontrolled flow between tanks. In this case valves, overflows and gate valves should be checked.
Alarm thresholds as rules
Alarms should have at least two levels: warning (for observation, an entry in the register) and alarm (requires a response). Rules for setting thresholds:
- base thresholds on real data from the installation from several weeks of normal operation, not on general values;
- avoid overly sensitive thresholds, because alarm overload leads to alarms being ignored;
- apply a time delay so that short disturbances do not trigger an alarm;
- combine signals: an alarm only on a simultaneous rise in pressure and level can better distinguish foam from an ordinary change in load;
- set a procedure: who receives the alarm, what they check and within what time.
Recording trends
Data on what happens over a week or a season are more valuable than a snapshot. Record the most important signals with a resolution from a few seconds to a minute, and keep aggregated values (hourly averages, minima, maxima) for longer. This makes it possible to compare winter with summer, the condition before and after a repair, and also to document actions in the event of an inspection or a dispute with the supplier.
Conclusion
Monitoring does not replace visual checks, but indicates where and when to look. Two or three signals read together, such as blower running hours, pressure between the membranes and roof level, are in practice enough for early detection of most membrane problems. A well-configured system reminds of an inspection before a defect becomes a failure.